110 VDC: The Invisible Power System Behind Substations, Telecom and Industry
Backup power conversations usually stay on the AC side: generators, UPS, transfer switches. Underneath runs a second system at 24, 48 and 110 volts DC. In substations, telecom exchanges and process plants, that DC bus decides whether anything else can react to a failure. At its centre sit two pieces of equipment most people never see: a station battery and a 110 VDC battery charger.
If the control voltage disappears with the grid, the protection scheme exists only on paper.
What runs on DC
Protection relays, circuit-breaker trip and close coils, SCADA and RTU panels, emergency lighting, fire and security panels and telecom equipment all draw from a battery kept on float by a charger. The design assumes the worst case. AC has gone, which is the exact moment the protection system exists for, and the DC bus must then run on battery alone long enough to trip breakers, report alarms to the control room and ride through the event.
A weak station battery costs more than convenience. A breaker that cannot trip during a fault turns a local problem into equipment damage, a wider outage or a fire.
| DC voltage | Typical application |
|---|---|
| 24 VDC | Control circuits, PLCs, small telecom |
| 48 VDC (−48 V) | Telecom exchanges, base stations, fibre nodes |
| 110 VDC | Substations, switchgear trip and close coils, protection relays |
| 220 VDC | Large substations and power stations |
Why an industrial charger is different
A commercial charger tops up a battery and switches off. An industrial charger is a continuously rated power supply. It carries the standing DC load and maintains the battery at the same time, using a constant-current then constant-voltage profile with float and boost stages matched to the battery chemistry.
A good industrial charger adds what a switchgear room needs: rectification rated for decades of continuous duty, temperature compensation for VRLA strings, earth-fault detection for the unearthed DC systems common in substations, and volt-free alarm contacts for charger failure, high or low DC voltage and earth faults, wired back to SCADA. On critical sites we install chargers as redundant pairs, so a charger failure becomes a maintenance ticket instead of a countdown. The three-phase 110 VDC / 50 A chargers we supply for switchgear rooms and industrial plants follow this pattern.
Chemistry follows the environment
Station batteries in hot, remote or unconditioned buildings are classic nickel-cadmium territory. NiCd tolerates heat, deep discharge and irregular charging that would ruin a VRLA string, and manufacturers such as Saft and ALCAD rate their industrial ranges for twenty years of service and more. In an air-conditioned switch room with a tighter budget, VRLA remains a sound choice as long as the room stays near 25 °C. Our article on UPS battery life and temperature explains why that number matters so much.
Size the battery from the real duty cycle: the momentary current when several trip coils operate together, the standing loads, motor-operated devices, and the autonomy your operator requires. IEEE 485 sets out the method for lead-acid batteries and IEEE 1115 for nickel-cadmium. A battery sized from a guess can look fine for years and then fall short on the one day it is asked to work alone.
DC systems fail quietly
Float voltage drifts, electrolyte dries out, terminals loosen, and an earth fault sits undetected on one pole. Nothing looks wrong until the bus has to carry the station by itself. The professional minimum is an annual inspection with cell-level voltage readings, terminal torque checks, charger calibration and earth-fault verification, plus periodic capacity testing that proves the battery can still deliver its rated ampere-hours.
Critical Energy Technologies engineers, supplies and maintains complete DC systems for utilities, telecom operators and industry in Jordan: industrial chargers, NiCd and VRLA station batteries, DC distribution and monitoring. See our battery and DC systems, then ask your team when the station battery last passed a capacity test. If nobody knows, start there.
DC systems in Jordan
Industrial battery chargers and DC systems we supply in Jordan
Critical Energy Technologies (CET) supplies 24, 48, 110 and 220 VDC industrial battery chargers across Jordan, from European manufacturers such as Salicru and from Sigma in Egypt, among others. We match each charger with the right station battery, Saft nickel-cadmium or EnerSys VRLA, in capacities from 5 Ah to 6,000 Ah, and commission the complete DC system for substations, switchgear rooms, telecom and industrial plants.
CET brings more than 10 years of hands-on experience in critical and emergency power supply to every project, from the first load survey to commissioning and maintenance. Call +962 77 564 7788, email info@critical-energy.net, or send us your load list for a sized quotation.
Spain · Chargers- SigmaEgypt · Chargers
France · NiCd
USA · VRLA

Comments are closed